If you’ve got an isolation valve on a main or riser that needs replacing, or one that won’t shut off any more, we can hold the water back on the live line and change the valve while the rest of the system keeps running. Call 1800 468 827 with the pipe size and material, and what the line feeds.
We’re an industrial and commercial contractor. We don’t do domestic work, so if it’s a tap, shower or toilet valve at home, you need a local plumber.
This is the one we hear about most from building services.
On the ground floor of a 26 storey tower in Southbank, a 250mm lugged valve on the 250mm condenser water riser wouldn’t close. The riser was running at 1,100 to 1,200 kPa and the bore was heavily tuberculated. We put an EZ2 insertion valve on the riser, its wedge sealed on the old pipe anyway, and the client got on with the valve change.
With a hot tap and a line stop, we tap the main, run a stop in through the fitting, swap the valve downstream and pull the stop out again.
The EZ2 needs clearance right around the pipe, so tight risers don’t always suit it. Where it fits, it mills a slot across the crown and leaves a permanent gate valve in the live line, so it also covers the case where there was never a valve there in the first place. It goes on steel, cast iron, ductile iron and some PVCs from 100mm to 300mm, and it’s rated to 1,600 kPa.
Or we freeze it. Liquid nitrogen jackets go on either side of the valve and form an ice plug in the pipe, with nothing welded on, which is handy where there’s no room for a fitting. We freeze steel, stainless, copper based alloys, ductile and cast iron.
At a shopping centre in Maroochydore we used a temporary line stop on a 150mm ductile iron domestic water main to fit a new isolation valve. The shops and restaurants kept trading, and there was very little room to work underground.
A logistics site at Eagle Farm in Brisbane needed a new isolation valve on a 200mm ductile iron main. That main fed several buildings and the site runs around the clock, so shutting it off would have stopped the lot. We hot tapped the main, put a line stop in through it and fitted the valve. Access was limited and heavy vehicles kept moving past us the whole time.
If you’re not sure whether your valve can be changed without a shutdown, just give us a call on 1800 468 827, we’ll ask a few questions and let you know.